CF-8 Chemical Feed Pump Controller
Monitoring fluid flow in:
- Air Conditioning Systems
- Industrial Refrigeration Systems
- Cooling in Data Centers
- Pools and Spas
- Chillers
- Scrubbers
- Fluid Blending Systems
- Water Treatment Systems
- Natural Gas
PIPE SIZE NPT |
NOMINAL ON/OFF SWITCH POINT RANGE (GPM) |
SHAFT LENGTH |
PADDLE NUMBER |
MODEL |
|
1″ |
5.0 – 3.0 |
- |
10512 |
CF-8N/-/10512 |
|
9.6 – 7.5 |
1 |
2 |
CF-8N/1/2 |
||
15.4 – 18.0 |
1 |
1 |
CF-8N/1/1 |
||
1 1/2" |
12.0 – 9.5 |
- |
10502 |
CF-8N/-/10502 |
|
14.2 – 11.8 |
2 |
3 |
CF-8N/2/3 |
||
19.0 – 13.5 |
- |
10570A |
CF-8N/-/10570A |
||
22.5 – 19.0 |
2 |
2 |
CF-8N/2/2 |
||
34.4 – 30.4 |
2 |
1 |
CF-8N/2/1 |
||
2" |
14.4 – 10.2 |
- |
10593 |
CF-8N/-/10593 |
|
14.4 – 10.2 |
- |
10566 |
CF-8N/-/10566 |
||
25.8 – 21.8 |
2 |
3 |
CF-8N/2/3 |
||
39.8 – 33.6 |
2 |
2 |
CF-8N/2/2 |
||
58.0 – 50.8 |
2 |
1 |
CF-8N/2/1 |
||
3" |
42.4 – 37.0 |
3 |
3 |
CF-8N/3/3 |
|
55.6 – 49.8 |
3 |
2 |
CF-8N/3/2 |
||
80.6 – 65.2 |
3 |
1 |
CF-8N/3/1 |
||
* /1G = Two Recepticals: one always on & one switched |
|||||
* /2G = Four Recepticals: two always on & two switched (shown) |
|||||
* Tee not included |
CF8 Group | CF-8-1G | ||||
CF-8-2G |
|||||
CF-8CR-1G |
|||||
CF-8CR-2G |
HYSTERESIS (Δ FLOW RATE TO ACTIVATE/DEACTIVATE SWITCH)
≈ 10% at upper end of flow range
≈ 30% at lower end of flow range
DIFFERENTIAL PRESSURE DROPS ACROSS UNIT
Under normal operating conditions:
≈ 1″–3″ pipe, less than 0.5 psi
≈ 4″–10″ pipe, negligible
WORKING LINE PRESSURE:
50 psi max., operating @ 180˚F 100 psi max. non-operating @ 180˚F Pressure over 50 psi can affect the switch point range
ELECTRICAL SWITCH CHARACTERISTICS
SPDT (single pole double throw) 13A, ½ hp @ 125VAC ½A @ 125VDC (tungsten lamp load) 10,000,000 Operations Median